| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| The WDB target agent debug service in Wind River VxWorks 6.x, 5.x, and earlier, as used on the Rockwell Automation 1756-ENBT series A with firmware 3.2.6 and 3.6.1 and other products, allows remote attackers to read or modify arbitrary memory locations, perform function calls, or manage tasks via requests to UDP port 17185, a related issue to CVE-2005-3804. |
| Multiple unspecified vulnerabilities on the Rockwell Automation AB Micrologix 1100 and 1400 controllers allow remote attackers to obtain privileged access or cause a denial of service (halt) via unknown vectors. |
| The web interface in the Rockwell Automation ControlLogix 1756-ENBT/A EtherNet/IP Bridge Module allows remote attackers to obtain "internal web page information" and "internal information about the module" via unspecified vectors. NOTE: this may overlap CVE-2002-1603. |
| Multiple cross-site scripting (XSS) vulnerabilities in the web interface in the Rockwell Automation ControlLogix 1756-ENBT/A EtherNet/IP Bridge Module allow remote attackers to inject arbitrary web script or HTML via unspecified vectors. |
| Open redirect vulnerability in the web interface in the Rockwell Automation ControlLogix 1756-ENBT/A EtherNet/IP Bridge Module allows remote attackers to redirect users to arbitrary web sites and conduct phishing attacks via unspecified vectors. |
| An
authentication bypass vulnerability exists in the affected product. The
vulnerability exists due to shared secrets across accounts and could allow a threat
actor to impersonate a user if the threat actor is able to enumerate additional
information required during authentication. |
| A security issue exists due to improper handling of malformed CIP Forward Close packets during fuzzing. The controller enters a solid red Fault LED state and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF015. To recover, clear the fault. |
| A security issue exists in FactoryTalk ViewPoint version 14.0 or below due to improper handling of MSI repair operations. During a repair, attackers can hijack the cscript.exe console window, which runs with SYSTEM privileges. This can be exploited to spawn an elevated command prompt, enabling full privilege escalation. |
| A denial-of-service vulnerability exists via the CIP/Modbus port in the Rockwell Automation Micro850/870 (2080 -L50E/2080 -L70E). If exploited, the CIP/Modbus communication may be disrupted for short duration. |
| A local code execution security issue exists within Studio 5000® Simulation Interface™ via the API. This vulnerability allows any Windows user on the system to extract files using path traversal sequences, resulting in execution of scripts with Administrator privileges on system reboot. |
| A security issue in the runtime event system allows unauthenticated connections to receive a reusable API token. This token is broadcasted over a WebSocket and can be intercepted by any local client listening on the connection. |
| A security issue exists due to improper handling of malformed CIP packets during fuzzing. The controller enters a hard fault with solid red Fault LED and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF019. To recover, clear the fault. |
| A security issue exists within DataMosaix™ Private Cloud, allowing attackers to bypass MFA during setup and obtain a valid login-token cookie without knowing the users password. This vulnerability occurs when MFA is enabled but not completed within a 7-day period. |
| A security issue exists due to improper handling of CIP Class 32’s request when a module is inhibited on the 5094-IF8 device. It causes the module to enter a fault state with the Module LED flashing red. Upon un-inhibiting, the module returns a connection fault (Code 16#0010), and the module cannot recover without a power cycle. |
| A security issue was discovered in DataMosaix Private Cloud, allowing users with low privilege to perform sensitive database operations through exposed API endpoints. |
| A denial-of-service security issue exists in the affected product and version. The security issue stems from a high number of requests sent to the web server. This could result in a web server crash however; this does not impact I/O control or communication . A power cycle is required to recover and utilize the webpage. |
| A security issue was found in the IPv6 stack in the Micro850 and Micro870 controllers when the controllers received multiple malformed packets during fuzzing. The controllers will go into recoverable fault with fault code 0xFE60. To recover the controller, clear the fault. |
| A Local Privilege Escalation vulnerability exists in the affected product. The vulnerability requires a local, low privileged threat actor to replace certain files during update and exists due to a failure to perform proper security checks before installation. |
| A security issue exists within the 5032 16pt Digital Configurable module’s web server. The web server’s session number increments at an interval that correlates to the last two consecutive sign in session interval, making it predictable. |
| A Remote
Code Execution vulnerability exists in the affected product. The vulnerability requires
a high level of permissions and exists due to improper input validation resulting
in the possibility of a malicious Updated Agent being deployed. |